TEST POINT CIRCUIT SATISFACTORY UNSATISFACTORY
VOLTAGE READINGS
READINGS
TP-1 Zone 1 Zero VDC 1.2 to 24 VDC
TP-2 Zone 2 Zero VDC 1.2 to 24 VDC
TP-3 Transfer relay Zero VDC 1.2 to 24 VDC
TP-4 Card supervision Zero VDC 1.2 to 24 VDC
TP-5 Short circuit Zero VDC 1.2 to 24 VDC
LED 4 Positive Ground LED OFF LED lit
Fault
LED 5 Negative Ground LED OFF LED lit
Fault
TP-8 RTI supervision Zero VDC 1.2 to 24 VDC
TP-11 Master Box Zero VDC 1.2 to 24 VDC
TP-12 Ground Fault Zero VDC 1.2 to 24 VDC
TP-13 Pwr Supply Fault Zero VDC 1.2 to 24 VDC
TP-14 Gen. Syst. Trbl Zero VDC 1.2 to 24 VDC
TP-15 Supv. of K4 relay Zero VDC 1.2 to 24 VDC
contacts
NOTE: All the above voltages are approximate and it is entirely possible to have a trouble condition
with readings other than shown. If your voltage readings differ and you cannot solve your trouble condition
by consulting this manual, please contact your local authorized FCI Distributor.
BMFC-6 Test Points
BMFC-6 TEST POINTS
(For location of a specific trouble)
INSTRUCTIONS:
Place negative ( - ) lead of DC voltmeter on Terminal 30 and positive (+) meter lead on indicated test point.