35B. THREE PHASE UNITS (except IST or STP units 
with VS2 or VS4 sufx): Connect the ground wire 
to the lug in the junction box. Connect any three 
wires from the pump to any three wires from the 
three-phase power source using the wire nuts 
supplied (from hardware pack p / n 400301902). 
Capacitors are not needed for three phase units. 
Install a pressure gauge in the line test port 
(see Figure 15), turn on the pump, and read the 
pressure gauge. Turn off the pump at the power 
supply, and change the connection of any two 
wires at the pump. Turn the pump back on and 
read the pressure gauge again. The electrical 
connection that gives the higher reading on the 
pressure gauge is the correct one.
35C. IST UNITS or STP units with a VS2 or VS4 sufx: 
Connect the ground wire coming from indoors to 
the ground lug in the junction box. Connect any 
three wires from the pump connector assembly to 
the three power wires coming from the Variable 
Frequency Controller (VFC). Capacitors are 
not needed for these units. Detailed installation 
instructions for the VFC should be referenced 
when connecting the VFC. These are supplied 
with the VFC.
Not installing a ground wire increases
the risk of lethal electric shock and
equipment failure. All holes of the
compression seal (contractors plug)
must be lled with wires or a celcon rod
to enable it to seal.
36.  Replace the junction box cover and tighten 
securely.
The pump discharge manifold has
two labeled ports: one for the syphon
system and one for the tank. A piston
leak detector must be vented to the tank
port (lower port) only. Do not connect a
piston leak detector to the syphon port
because this will make the leak detector
inoperative, resulting in an increased
risk of contamination of the environment
(see tank port in Figure 14).
37.  Connect power to the submersible pump at the 
electrical supply box.
38.  Test proper operation by dispensing product into 
calibration can.
39.  Turn off the dispenser switch. Feel the 
submersible pump to make sure that the pump has 
stopped running.
Note: If the pump does not turn off when the dispenser 
switch is turned off, this may indicate an electrical 
problem in the dispenser or other wiring error or 
malfunction. Call this to the immediate attention of 
a qualied electrician.
40.  Visually check for leaks on the manifold head 
during pump operation and after.
41.  Install a pressure gauge in the line test port to 
ensure that the STP / IST is providing proper line 
pressure. 
42.  Turn on the STP / IST. While running, the pressure 
should be above 24 psi (1.65 bar). PMA size will 
affect psi. 
43.  Turn off the STP / IST and verify that the line 
pressure is holding. 
44.  Remove the pressure gauge and replace the plug. 
45.  Turn on the STP / IST and, again, visually check for 
any leaks.