9
VF5
AUTOMATIC DOORS FOR LIFTS
LEARNING PHASE OF THE DOOR OPERATOR
1 Switch on the VF door controller.
- Button O/I in the side of the box.
2 Cables.
- 5 / 6 / 7 Connect the 230 V AC mains supply to the controller
- If they are connected, disconnect the following connections:
8-12: Input signals.
21/23/25/26: Priority inputs.
30- 41: Outputs.
3 Program in ”2 INPUTS” (switch 1 = OFF) and “MASTER” (switch 4 = ON).
4 Program the door type.
Switch 2: Landing door type (semiautomatic = OFF or automatic = ON).
Switch 3: Rotation sense.
5 Adjust the 3 potentiometers in maximum (maximum to the right 52, 53, 54)
With these regulations, the door overcomes little mechanic frictions, but if they are very important
is not possible to x it.
If the door does not move with this conguration, then there is a mechanical problem or electric
(motor or controller not supplied).
6 Place the door in a middle position in order to see the starting movement.
7 Switch on the VF unit (O/I button on the controller).
The door must remain stopped. If the door moves, verify the position of switch 1.
8 Press once the «AUTOADJUSTMENT» button to start a learning cycle.
The correct steps that the door has to make are:
- The door should close completely (the «CLOSED» LED lights on).
- Then the door opens completely (during this phase, the OK Status led will blink synchronized with
the encoder pulses to check it visually) and after a open pause of 3s the door closes again (OK LED
blinks normally).
- The door keeps closed with CLOSED LED and relay on. The skate is completely closed and the
«OK» LED blinks normally.
9 Door Test.
- Press once the «TEST» button and the door will open, and it will close pressing again the button.