BLUEHELIX TECH RRT 28 C
27EN
cod. 354M1070 - Rev. 01 - 07/2018
P34 Pump operation 0-3 = Operation strategy 2
P35 Modulating pump min. speed 30-100% 30%
P36 Modulating pump start speed 90-100% 90%
P37 Modulating pump max. speed 90-100% 100%
P38
Pump deactivation temperature during Post-Circu-
lation (b01=1)
0-100°C 50°C
Pump deactivation temperature during Post-Circu-
lation (b01=2)
0-100°C 55°C
Pump deactivation temperature during Post-Circu-
lation (b01=3)
0-100°C 55°C
Pump deactivation temperature during Post-Circu-
lation (b01=4)
0-100°C 55°C
P39
Pump activation hysteresis temperature during
Post-Circulation (b01=1)
0-100°C 10°C
Pump activation hysteresis temperature during
Post-Circulation (b01=2)
0-100°C 25°C
Pump activation hysteresis temperature during
Post-Circulation (b01=3)
0-100°C 25°C
Pump activation hysteresis temperature during
Post-Circulation (b01=4)
0-100°C 25°C
P40 Heating user max. setpoint 20-90°C 80°C
P41 Max. output in heating 0-100% 80%
P42
Burner shutdown in DHW (b01=1) 0=Fixed, 1=Linked to setpoint, 2=Solar 0=Fixed
Legionella protection (b01=2)
0-7=Days of activation (1 = Once every 24 hours /
7= Once every 168 hours)
0=No protection
Burner shutdown in DHW (b01=3) 0=Fixed, 1=Linked to setpoint, 2=Solar 0=Fixed
Legionella protection (b01=4) 0-7=Activation days 0=No protection
P43
Comfort activation temperature (b01=1) 0-50°C 40°C
Hot water tank hysteresis (b01=2) 0-60°C 2°C
Comfort activation temperature (b01=3) 0-80°C 40°C
Hot water tank hysteresis (b01=4) 0-60°C 2°C
P44
Not used (b01=1) Do not modify 0
Primary setpoint (b01=2)
70-85°C (Primary circuit temperature adjustment in
DHW)
80°C
Comfort deactivation hysteresis (b01=3) 0-20°C 20°C
Primary setpoint (b01=4)
70-85°C (Primary circuit temperature adjustment in
DHW)
80°C
P45
DHW standby time (b01=1) 30-255seconds 120seconds
DHW standby time (b01=2) 30-255seconds 120seconds
DHW standby time (b01=3) 30-255seconds 120seconds
DHW standby time (b01=4) 30-255seconds 120seconds
P46
DHW user max. setpoint (b01=1) 40-70°C 55°C
DHW user max. setpoint (b01=2) 40-70°C 65°C
DHW user max. setpoint (b01=3) 40-70°C 55°C
DHW user max. setpoint (b01=4) 40-70°C 65°C
P47
DHW pump Post-Circulation (b01=1) 0-255seconds 3seconds
DHW pump Post-Circulation (b01=2) 0-255seconds 30seconds
DHW pump Post-Circulation (b01=3) 0-255seconds 30seconds
DHW pump Post-Circulation (b01=4) 0-255seconds 30seconds
P48 Max. output in DHW 0-100% 100%
P49
Comfort1 standby time (b01=1) 0-100minutes 20minutes
Not implemented (b01=2) -- --
Not implemented (b01=3) -- --
Not implemented (b01=4) -- --
Contents Description Range Default