FIRECLASS Fire detection system Panel Accessories
Fixing instructions Doc. version 1.0 1/12
Installing the FireClass FC700 Series
POS800/PCS800 Ethernet Switch
Introduction
This leaflet covers the installation of an Ethernet
Switch (an optional accessory) on the following
FireClass panels:
FC708D
FC718D
FC702D
FC702S (PCS800 only)
Table 1 outlines the three Ethernet switch types
available.
The FireClass POS800-S and POS800-M
Ethernet switches are used to connect devices
(for example a panel and an AC repeater) with a
single, redundant optical or metallic layer.
The POS800-S/POS800-M Ethernet switch has
four 10/100Base-T(X) RJ45 ports that connect it
to the FC-FI board, the primary graphical user
interface (GUI) and additional AC/ DC repeaters.
The switch also has two optical ports that can
connect an AC repeater using a redundant (or a
single) optical path if you require redundant wir-
ing or long distance wiring. After you connect the
Ethernet switch, configure it. Refer to the “Con-
figuring the POS800-S and POS800-M Ethernet
switches” section.The total maximum number
of devices on the network is 254 and this is split
between all devices (repeaters, the FC-FI board
and Ethernet switches). For the maximum num-
ber of LNET GUI repeaters, refer to the latest
FireClass Express documentation.
The FireClass PCS800 Ethernet switch provides
five 10/100Base-T(X) RJ45 ports that connect it
to the FC-FI board, the primary GUI and addi-
tional AC/DC repeaters. The PCS800 does not
require additional configuration.
Refer to Table 2 for limiting distances for each
type of cable.
Ethernet Switches allow the use of a dual power
supply to provide backup power in the event of,
for example, a component failure or a blown
fuse. Note that there is one power rail in the
panel.
Switch
Type
Optical Ports Copper
Ports
POS800-S 2x 100Base-FX
(Single Mode)
4x 10/
100Base-T(X)
RJ45 Ports
POS800-M 2x 100Base-FX
(Multi-Mode)
4x 10/
100Base-T(X)
RJ45 Ports
PCS800 - 5x 10/
100Base-T(X)
RJ45 Ports
Table 1: Ethernet switch types
Switch
Type
Limiting Dis-
tance (Opti-
cal)
Limiting Dis-
tance (Cop-
per)
[1]
POS800-S 30km 100m
POS800-M 2km 100m
PCS800 - 100m
Table 2: Limiting distances
[1] Limiting distances without a repeater. The distance
can increase if a switch or a repeater is used.
CAUTION
Before you install an Ethernet switch,
ensure that the panel is isolated from
the mains supply and it is not running on
batteries.
Question and Answer IconNeed help?

Do you have a question about the FireClass FC700 Series and is the answer not in the manual?

FireClass FC700 Series Specifications

General IconGeneral
Power Supply100-240VAC, 50/60Hz
PoE StandardIEEE 802.3af/at
Jumbo Frame SupportYes
VLAN SupportYes
Quality of Service (QoS)Yes
ManagementWeb, CLI
Security FeaturesPort Security, Access Control Lists (ACLs)
Operating Temperature0°C to 50°C
Power over Ethernet (PoE)Available on some models

Summary

Installing the FireClass FC700 Series POS800/PCS800 Ethernet Switch

Introduction

This leaflet covers the installation of an Ethernet Switch (an optional accessory) on FireClass panels.

Installing the Ethernet Switch (POS800/PCS800) on a FireClass Panel

Installation Steps

Step-by-step guide for mounting and connecting the Ethernet switch to FireClass panels.

Configuring the POS800-S and POS800-M Ethernet switches

Configuration Caution

Ensures the panel is isolated from mains and not running on batteries before configuration.

Cable Examples