Fireray One Parameters Minimum Typical Maximum Unit
Operating Voltage 14 - 36 V
Operating Current 4.5 5.0 5.5 mA
Operating Current – Alignment Modes 31 33 35 mA
Response Thresholds (25%, 35%, 55%, 85%)
(note – only 25% and 35% are EN54-12 approved)
1.25
25
1.87
35
8.24
85
dB
%
Delay to Alarm - 10 - s
Delay to Fault - 10 - s
Operating Distance (Separation between Detector and
Reflector) (4 reflectors required for >50m, >164ft)
5
16
- 120
394
m
feet
Rapid Obscuration Fault Threshold - 85 - %
Maximum angular alignment range of detector - - ±4.5 Deg
Tolerance to beam misalignment (per EN54-12) – Detector - ±0.5 - Deg
Tolerance to beam misalignment (per EN54-12) – Reflector - ±5 - Deg
Optical Wavelength - 850 - nm
Operating Temperature -20
-4
-
-
+55
+131
°C
°F
Storage Temperature -40
-40
-
-
+85
+185
°C
°F
Relative Humidity (non-condensing) - - 93 %RH
IP rating - 55 - -
Fire & Fault Relays (VFCO, Resistive) - Contact voltage - - 30 V DC
Fire & Fault Relays (VFCO, Resistive) - Contact current - - 2 A
Cable gauge 22
0.5
-
-
14
1.6
AWG
mm
Housing flammability rating - UL940 V0 - -
Fireray One Dimensions and Weights Width (mm) Height (mm) Depth (mm) Weight (kg)
Reflective Detector, including detector base 134 182 151 0.7
Reflector 100 100 10 0.1
Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the
European Union. For proper recycling, return
this product to your local supplier upon the
purchase of equivalent new equipment, or
dispose of it at designated collection points. For
more information see: www.recyclethis.info.
Equipment Disposal