EasyManua.ls Logo

FIREtec FTEP SERIES - Page 10

FIREtec FTEP SERIES
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
When entering Level 3
Start at ZONE LATCH – Each zone is
individually set as either Latching or Unlatching.
Starting with Zone 1 led flashing (zone 1 is latching)
PRESS Key 2 (Change Setting) – moves flashing
Led to make ‘Zone 1 UNLATCHING’
PRESS Key 1 (Function)moves setting (flashing
led) to the next zone.
Repeat above process to set remaining zones.
On the last zone, Press Key 1 (Function) moves
setup to setting the Zone Type – 470R or Short CCT.
Zone Type – The fire detection type of each zone
is set as either 470R or Short Circuit
(default setting is 470R)
Starts at Zone 1 led flashing (Zone 1 is 470R)
PRESS Key 2 (Change Setting) – moves flashing
led to make ‘Zone 1 Short CCT’
PRESS Key 1 (Function) – moves setting (flashing
led) to the next zone.
Key 2 -change setting to 470R or Short CCT.
Repeat above process to set remaining zones.
On the last zone, press Key 1 (Function) moves setup
to setting Monitor Input.
Setting Monitor Input – This is an input that when
set up requires 24Vdc applied to the terminal. If not
a fault is generated and the ‘common fault’ LED
is illuminated.
Monitor input can either be ON or OFF – if it is off
the input is not monitored and 24Vdc does not have
to be applied to the terminal.
PRESS Key 2 (Change Setting) – moves flashing
led to make Monitor Input either ON or OFF.
PRESS Key 1 (Function) – moves setting (flashing
led) to Class Change.
Setting Class Change – Set up to illuminate the
‘common fire’ led when Class Change is activated.
It can be set to either ON or OFF – if it is set to OFF
The ‘common fire’ led is NOT illuminated when
Class Change is activated.
PRESS Key 2 (Change Setting) – moves flashing
led to make option either ON or OFF.
PRESS Key 1 (Function) – moves setting (flashing
led) to Alarm Delay.

Related product manuals