To reduce the risk of injury, user must read and understand the operator's manual for their Natural
Gas (NG) generator and this manual. Ensure combability and fit before using any
accessory. Do not use an accessory if a port is damaged or missing. If you are not comfortable
performing any of the functions described in this manual, take your unit to an authorized
service center.
IMPORTANT SAFETY INFORMATION
WARNING
This product is intended only for use outdoors with portable Natural Gas (NG) generator that
may be moved for convenience of operation. Connected hose assembly shall be of adequate
length and capacity for the intended application.
Connection to outdoor gas piping must be done by a certified plumber.
Installation must be made in accordance with any local codes or regulations, or in the absence of
local codes or regulations, in accordance with the National Fuel Gas Code (NFPA 54/ANSI Z223.1).
The hose and fittings should be visually inspected periodically to determine that they have not
been damaged and are suitable for continued use.
The hose and fittings are designed for movement after installation, but must not be kinked, twisted
or torqued.
Protect hose and fittings from dust, dirt, and damage when not in use. Insert plastic plug in the
socket and the cap over the hose end plug whenever the hose is removed from socket.
If your home has no outside Natural Gas (NG) piping, a connection must be installed by a certified
plumber in accordance with any local codes or regulations, or in the absence of local codes or
regulations, in accordance with the National Fuel Gas Code (NFPA 54/ANSI Z223.1).
The hose assembly, fittings, valves and adapters must be inspected and tested (leak test) before
each use for leaks or sign of damages.
Only use the provided quick connect adapter with provided hose assembly.
Remember that whichever fuel delivery system or type of vapor fuel used, the fuel pressure at the
demand regulator installed on the engine generator must be between 0.25 and 0.40 PSI. (7-11
inches of water column or 4 and 6 oz. of water column). Any lower pressure and the unit will starve
for fuel under load. If the hose and quick connect adapter are properly connected and still not
getting gas, delivery pressure needs to be verified. For pressure greater than 0.5 PSI, make sure
that an in-line regulator is present. This additional regulator is NOT provided with this kit. Another
concern would be rating if hose and quick connect adapter. Both the hose and the quick connect
adapter are only rated to 0.5 PSI.
LEAK TEST INSTRUCTION:
DANGER
Natural Gas (NG) is highly flammable and explosive. Fire or explosion can cause sever burns or
death or property damage.
-DO NOT use open flame to test for gas leaks.
-DO NOT perform leak test near any potential source of ignition.
-DO NOT smoke while performing leak test.
English Customer Service: 1-844-FIRMAN1
02

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Firman 1805 and is the answer not in the manual?

Firman 1805 Specifications

General IconGeneral
BrandFirman
Model1805
CategoryCables and connectors
LanguageEnglish

Related product manuals