Diagnostic Connections (figure 8)
FlowScannert valve diagnostics system hook‐up.
Includes connector body and body protector. If
ordered for units with gauges, a stem is also included.
Note
Part numbers are shown for recommended spares only. For part
numbers not shown, contact your Emerson Process Management sales
office.
Description
For 3582 pneumatic valve positioners
 For units w/gauges
  SST fittings
  brass fittings
 For units w/o gauges
  SST fittings
  brass fittings
For 3582i electro‐pneumatic valve positioners
 For units w/gauges
  SST fittings
  brass fittings
 For units w/o gauges
  SST fittings
  brass fittings
Loop Schematics
This section includes loop schematics required for wiring of intrinsically safe installations. If you have any questions,
contact your Emerson Process Management sales office.
GE28591 Rev A
NOTES:
1. BARRIERS MUST BE CSA CERTIFIED WITH ENTITY PARAMETERS
 AND ARE TO BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S I.S. INSTALLATION INSTRUCTIONS.
2. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
 CANADIAN ELECTRICAL CODE, PART I.
3. FOR ENTITY INSTALLATION (I.S. AND N.I.): Vmax > Voc, Imax > Isc
 Ci + Ccable < Ca, Li + Lcable < La
Figure 28. CSA Loop Schematic for Fisher 582i Converter (Installation drawing GE28591)