EasyManua.ls Logo

Fisher 3660 - IECEx

Fisher 3660
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Instruction Manual
D101402X012
3660 and 3661 Positioners
September 2015
7
Table 5. Hazardous Area Classifications for Fisher 3661 Positioner—ATEX
Certificate Certification Obtained Entity Rating Temperature Code
ATEX
II 1 G
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 Ga
Ui = 30 VDC
Ii = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb 82°C)
T5 (Tamb 62°C)
T6 (Tamb 47°C)
II 3 G
Type n
Gas
Ex nA IIC T6 Gc
- - - T6 (Tamb 62°C)
IECEx
Conditions of Certification
Intrinsically Safe
WARNING
Substitution of components may impair intrinsic safety.
-40_C Ta +82_C; T6 (Ta +47_C); T5 (Ta +62_C)
Entity Parameters
Ui
=
30 V, li = 150 mA, Pi = 1.25 W, Ci = 0 nF, Li = 0 mH
Type n
WARNING
Disconnect power before opening.
-40_C Ta +82_C; T6 (Ta +82_C)
Refer to table 6 for additional approval information.
Table 6. Hazardous Area Classifications for Fisher 3661 Positioner—IECEx
Certificate Certification Obtained Entity Rating Temperature Code
IECEx
Intrinsically Safe
Gas
Ex ia IIC T4/T5/T6 Ga
Ui = 30 VDC
Ii = 150 mA
Pi = 1.25 W
Ci = 0 nF
Li = 0 mH
T4 (Tamb 82°C)
T5 (Tamb 62°C)
T6 (Tamb 47°C)
Type n
Gas
Ex nA IIC T6 Gc
- - - T6 (Tamb 82°C)

Related product manuals