Refrigerant pipe installation 
Installation  103
 
 
4.3 Install the Unit 
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling. 
Never hold the inlet of the outdoor unit to prevent it from deforming. 
Do not touch the fan with hands or other objects. 
Do not lean it more than 45, and do not lay it sidelong. 
Make concrete foundation according to the specifications of the outdoor units. 
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind. 
 
 
5.  Refrigerant pipe installation 
5.1 Maximum pipe length and height drop 
Considering the allowable pipe length and height drop to decide the installation position. Make sure the 
distance and height drop between indoor and outdoor unit not exceeded the date in the following table. 
Model  Max. Length  Max. Elevation 
12,000Btu/h 25m  10m 
18,000Btu/h 30m  20m 
24,000Btu/h~30,000Btu/h 50m  25m 
36,000Btu/h ~60,000Btu/h  65m  30m 
 
5.2 The procedure of connecting pipes 
5.2.1  Choose the pipe size according to the specification table. 
5.2.2  Confirm the cross way of the pipes. 
5.2.3  Measure the necessary pipe length. 
5.2.4  Cut the selected pipe with pipe cutter 
  Make the section flat and smooth. 
90
Lean
Crude
Burr
o