Electrical Control Function 
Electrical Control System  117
1.  Electrical Control Function 
1.1 Definition 
T1:  Indoor room temperature 
T2:    Coil temperature of indoor heat exchanger middle. 
T2B: Coil temperature of indoor heat exchanger outlet. 
T3:    Coil temperature of condenser 
T4:  Outdoor ambient temperature 
T5:  Compressor discharge temperature 
1.2 Main Protection 
1.2.1 Time delay at restart for compressor. 
1.2.2 Temperature protection of compressor discharge 
When the compressor discharge temp. is getting higher, the running frequency will be limited as below rules: 
12K     18~60K 
T5
Compressor off
Frequency limit1
F
E
D
C
Frequencies increase slowly
B
Normal
A
Frequency holding
Frequency limit2
 
T5
Compressor off
Frequency lim it
Normal
Frequency holding
 
1.2.3 Sensor protection at open circuit and breaking disconnection. 
1.2.5 Indoor fan delayed open function 
When the unit starts up, the louver will be active immediately and the indoor fan will open 7s later. 
If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind function. 
1.2.6 Fan speed is out of control 
For console: 
When indoor fan speed keeps too low (300RPM) for certain time, the unit will stop and the LED will display 
the failure.   
For other models: 
When indoor fan speed keeps too low (lower than 300 RPM) for 50s, the indoor fan will shut off and restart 
30s later, if protection happened 3 times when fan motor restart continuously, the unit will stop and the LED 
will display the failure.