EasyManua.ls Logo

FläktGroup eQ PRIME 032 - Fire, Fan, and Filter Alarms

Default Icon
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
55FläktGroup DC_9355GB 20180119_R0 We reserve the right to make changes without prior notice
Alarm guide
Continued on next page
Alarms Alarm text Cause Action Type
Alarm electric heater El htg alarm:
Alarm
Terminal blocks 67-68 in
control cabinet indicate
alarm, normally caused by
thermal overload protection
in the electric heater.
• Check thermal overload protection
in electric heater.
• Check contact function for digital
input 2, compare with function
obtained from electric heater.
A
Alarm recovery unit Heat recovery
alarm: Alarm
• See other alarm points from the recovery
unit for further details.
B
Low voltage to rotor
operation
Hrec. Unit Volt low:
Alarm
The incoming supply
voltage is too low for rotor
operation.
• Check the supply voltage.
C
High voltage to rotor
operation
Hrec. Unit Volt
high:
Alarm
The incoming supply
voltage is too high for rotor
operation.
• Check the supply voltage.
C
Broken rotor belt Hrec. Unit
Brokenbelt:
Alarm
The drive belt on the rotor
has become detached or
loose.
• Check that the drive belt has not
become detached or loose.
C
Rotor motor
locked/blocked
Hrec. Unit Motor
blocked:
Alarm
The rotor moves too slowly
or is jammed.
• Check that the rotor is not moving more
slowly than usual and is not jammed.
C
Faulty sensor on
rotor motor
Hrec. Unit Sensor
error:
Alarm
Faulty sensor in rotor motor. • Contact FläktGroup support. C
High temperature in
rotor motor
Hrec. Unit High
temp:
Alarm
Motor has been running hot. • Check that the rotor is not moving more
slowly than usual and is not jammed.
C
DIP switch error in
rotor operation
Hrec Unit DIP error:
Alarm
DIP switch has
unauthorised setting.
• Reset to factory setting.
C
Cooling pump alarm Cooling pump
alarm: Alarm
Terminal blocks 61-62 in
control cabinet indicate
alarm, normally caused
by motor protection in the
chilled water circulation
pump.
• Check motor protection in chilled water
circulation pump.
• Check contact function for digital input 1,
compare with function obtained from pump.
B
Alarm DX cooling Cooling DX
alarm
Terminal blocks 61-62 in
control cabinet indicate
alarm, normally caused by
alarm from condenser.
• Check alarm from condenser.
• Check contact function for digital input 1,
compare with function obtained from
condenser.
B
Alarm supply air filter Supply filter alarm The measured differential
pressure over the supply
air filter exceeds the set
alarm level, normally due
to soiling.
• Check the supply air filter and replace if
necessary.
• If the pressure drop over the supply air filter
is too high or too low in relation to the desired
final pressure drop. Adjust the alarm level
using the handheld terminal.
B
Alarm, extract air
filter
Exhaust Filter
alarm
The measured differential
pressure over the extract
air filter exceeds the set
alarm level, normally due
to soiling.
• Check the extract air filter and replace if
necessary.
• If the pressure drop over the extract air
filter is too high or too low in relation to
the desired final pressure drop.
Adjust the alarm level using the handheld
terminal.
B
14