MAINTENANCE INSTRUCTIONS
Servicing Notes
Servicing should be carried out annually by a competent person such as a
Corgi registered engineer.
The service should include visually checking the chimney and fire opening for
accumulations of debris and a smoke test to check for positive up-draught in
the chimney.
The condition of the ceramic should be checked and if necessary the whole
set should be replaced with a genuine replacement set.
After any servicing work a gas soundness check must always be carried out.
4.1 GENERAL ACCESS FOR SERVICING
4.1.1 TO REMOVE THE OUTER CASE.
a) Prepare work area (lay down dustsheets etc.)
b) Remove control knob.
c) Remove two lower outer case fixing screws, and the two upper outer
case fixing screws (see fig.7 & 8) and lift the case upwards and away.
d) Remove the radiants and move to a safe place
e) Re-assemble in the reverse order.
Fig. 7 Removing the Lower Outer Case Fixing Screws
16