3.0 Operation, continued
3.2 Audible Alarms and Visual Indicators
The table below details the audible alarms and visual indicators of the FPR1207-F.
Table 3-1, Audible Alarms and Visual Indicators
3.3 Battery
Battery construction varies signicantly between manufacturers. Alpha Technologies
recommends the use of qualied batteries only.
Part Description
AX-STDBAT-7 Battery 7.2Ah AGM, 1-year Warranty
AX-LONGBAT-7 Battery 7.2Ah AGM, 3-year Warranty
AX-LONGBAT-8 Battery, Longlife, 8Ah, AGM 3-year Warranty
Condition Status LED
Audible
Alarm
Description
NORMAL System LED (GREEN) N/A
Condition normal; AC powers load,
charges battery.
ON BATTERY
Battery LED (GREEN)
ash
(1) 1s beep on loss
of AC
Input fails; battery powers load.
LOW BATTERY RED LED blinking
When AC is available,
audible alarms are
suppressed. When AC
fails, 1 beep every 15s.
When battery capacity is < 25%,
unit triggers alarm, or when the
“Battery Emergency Use” button
is pressed.
REPLACE BATT RED LED steady
2 beeps, every 15
minutes
Every 180 days, the unit will
automatically initiate a battery
test. The test lasts approx. 60
min., and LED lights if battery
replacement is needed.
BATT MISSING RED LED blinking N/A
Approximately 20s after battery
removal, system initiates battery
detection routine. Battery detection
runs every 30s when oat
charging. Upon verication, alarm
tripped.
010-344-B1-001 Rev. A (2/2014)
14