DIP
switch
Function ON Function OFF
#6 Electrical override ON Electrical override OFF
#5 No function No function
#4 Equal percentage Linear
#3 Normally Open Normally Closed
#2 Control signal 2-10V Control signal 0-10V
#1 Auto cycle ON Auto cycle OFF
6
5
4
3
2
1
%%
%%
%%
%%
%%
%%
%%
%%
%%
%%
DIP
switch
Function ON Function OFF
#8 Terminal resistor active Terminal resistor inactive
#7 Modbus BACnet
#6 BIT 5 = 1 BIT 5 = 0
#5 BIT 4 = 1 BIT 4 = 0
#4 BIT 3 = 1 BIT 3 = 0
#3 BIT 2 = 1 BIT 2 = 0
#2 BIT 1 = 1 BIT 1 = 0
#1 BIT 0 = 1 BIT 0 = 0
6
5
4
3
2
1
8
7
Modbus
Address
setting
Address
setting
BACnet
Modbus
Address
setting
Address
setting
BACnet
Modbus BACnet
1
1
1
1
1
1 0
0
0
0
0
0
DIP Switch Settings
The valve functions are set on DIP switches found under the connection cover. PCB mounted electri-
cal components will not be directly exposed when DIP switches are to be set. Factory setting for all
switches is OFF.
FlowCon FN.0.2 Actuator
FlowCon FN.0.2-BUS Actuator
This paper is a supplement to the FlowCon General Instruction
Latest release of any FlowCon material is available on www.owcon.com
FlowCon FN.0.2, FN.0.2-BUS and FN.0.4
1B95080 - 01/2023
Page 4 of 8