
Do you have a question about the FlowCon FN.0.2 and is the answer not in the manual?
| Brand | FlowCon |
|---|---|
| Model | FN.0.2 |
| Category | Controller |
| Language | English |
Do not connect power before fitting the actuator or install in closed position to prevent valve damage.
Mount actuator on valve and finger tighten the connection union. Do not use additional tools.
Electrically open actuator via DIP switch #6 (FN.0.2/FN.0.4) or retract spindle (FN.0.2-BUS) before loosening union.
Upside-down installation is permitted along with standard horizontal and vertical orientations.
Wiring details for FN.0.2 0-10V modulating actuator, including input and feedback signals.
Wiring diagram for FN.0.2-BUS actuator using RS-485 serial communication (D+, D-, P1, P2).
Wiring for FN.0.4 2-Position (Normally Closed) and 3-Point Floating (Normally Closed) actuators.
Actuator calibrates to closing point upon power-up, then enters normal operation mode.
Prevents valve jamming by performing 50% stroke cycle every 3 weeks if no movement occurs.
Activates valve full opening via DIP switch #6, indicated by blinking red/green LED.
Allows manual valve operation (open/close) using a magnet on the actuator's right side.
Temporarily opens valve fully, independent of control signal, for system flushing.
Configuration of DIP switches #1-6 for FN.0.2 functions like override, signal type, and auto cycle.
Settings for FN.0.2-BUS DIP switches #1-8 for Modbus/BACnet, BIT settings, and terminal resistor.
LED indications for FN.0.2: green (normal), blinking green (calibration), blinking red/green (override), red (failure).
LED indications for FN.0.2-BUS: green (normal), flickering green (bus comms), blinking yellow (manual spindle).
LED indications for FN.0.4: green (normal), blinking green (calibration), blinking red/green (override), red (failure).
Forced re-calibration via DIP switch #6 toggle or electrical 10V-2V signal sequence.
Re-calibration via BACnet (MSV.1=2) or Modbus (register 138=1).
Forced re-calibration via DIP switch #6 toggle.
Setting Baud Rate, DIP switches, MAC address, and selecting PICV valve type and control mode.
Checking Current Flow, Status Information, Error Information, and service commands via bus.
Loading...