Re-Calibration
FN.0.2
Re-calibration can be achieved in one of 2 ways:
1. Forced individual actuator re-calibration can also be performed by flipping DIP switch #6
from OFF to ON and back to OFF on the relevant actuator.
2. Forced concurrent re-calibration for all modulating actuators is electrically possible. Within 60
sec. provide the following electrical control signal sequence to the grey wire: 10V-2V-10V-2V-
10V-2V to achieve re-calibration.
After re-calibration the actuator will go into normal operation mode.
FN.0.2-BUS
For FN.0.2-BUS change MSV.1 to 2 (BACnet) or register 138 to 1 (Modbus).
After re-calibration the actuator will go into normal operation mode.
FN.0.4
Forced individual actuator re-calibration can also be performed by flipping DIP switch #6 from OFF
to ON and back to OFF on the relevant actuator.
After re-calibration the actuator will go into normal operation mode.