EasyManua.ls Logo

Flowserve Limitorque MX Device Net Field Unit - Di_Position_And_Bus_Mode_Chan; Di_Position_Chan; Di_Actuator_Faults_1_Chan

Flowserve Limitorque MX Device Net Field Unit
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
4.2.1 DI_Position_and_Bus_Mode_Chan
Table 4.12
Value Definition
0x21 Remote + Opened
0x22 Remote + Closed
0x24 Remote + Opening
0x28 Remote + Closing
0x30 Remote + Stop
0x41 Local + Opened
0x42 Local + Closed
0x44 Local + Opening
0x48 Local + Closing
0x50 Local + Stop
0x81 Stop + Opened
0x82 Stop + Closed
0x84 Stop + Opening
0x88 Stop + Closing
0x90 Stop + Stop
4.2.2 DI_Position_Chan
Table 4.13
Bit 7  Bit 6  Bit 5  Bit 4  Bit 3  Bit 2  Bit 1  Bit 0 
Reserved Reserved Reserved Stop Closing Opening Closed Opened
Table 4.14 – Possible values of DI_Position_Chan
Value Definition
0x01 Opened
0x02 Closed
0x04 Opening
0x08 Closing
0x10 Stop
4.2.3 DI_Actuator_Faults_1_Chan
Table 4.15
Bit 7  Bit 6  Bit 5  Bit 4  Bit 3  Bit 2  Bit 1  Bit 0 
Reserved Reserved Motor Over
Temp
Phase Error Over Torque Manual
Moved
Valve
Jammed
Monitor