Limitorque MX DeviceNet Field Unit FCD LMENIM2328-00 – 11/05
flowserve.com
Table 4.32 – Continued
Attribute ID  Access Rule  Name  Data Type  Description  Semantics of Value 
20 RO TQ_Status_4 UINT MB_TQ_Open_
Breakout_Last
Engineering Use
21 RO TQ_Status_5 UINT MB_TQ_Close_
Breakout_Last
Engineering Use
22 RO TQ_Status_6 UINT MB_TQ_Open_
Ending_Last
Engineering Use
23 RO TQ_Status_7 UINT MB_TQ_Close_
Ending_Last
Engineering Use
24 RO TQ_Status_8 UINT MB_TQ_Close_
Peak_Last
Engineering Use
25 RO TQ_Status_9 UINT MB_TQ_Open_
Peak_Last
Engineering Use
26 RO TQ_Status_10 UINT MB_TQ_Open_
Breakout_Ref
Engineering Use
27 RO TQ_Status_11 UINT MB_TQ_Close_
Breakout_Ref
Engineering Use
28 RO TQ_Status_12 UINT MB_TQ_Open_
Ending_Ref
Engineering Use
29 RO TQ_Status_13 UINT MB_TQ_Close_
Ending_Ref
Engineering Use
30 RO TQ_Status_14 UINT MB_TQ_Close_
Peak_Ref
Engineering Use
31 RW Travel_Limit_Low UINT Lower limit of the
valve position in
percent of travel
span
Range 0 – 1000
Default = 0
32 RW Travel_Limit_Up UINT Upper limit of the
valve position in
percent of travel
span
Range 0 – 1000
Default = 0
33 RW Valve_Maint_ Date SHORT-
STRING
Date of last valve
maintenance
String length is limited
to 16 char. Default = 0
(empty)
34 RW Valve_Serial_Num SHORT-
STRING
Serial number of
the valve belonging
to the positioner of
electronic device
String length is limited
to 16 char. Default = 0
(empty)
35 RO Valve_status_0 WORD Requested relay
channel value
Default = 0
36 RO Valve_status_1 WORD Status Register
– Modbus Register
9
Default = 0
37 RO Valve_status_2 WORD Fault Register
– Modbus Register
10
Default = 0
38 RO Valve_status_3 WORD Digital Output
Register – Modbus
Register 11
Default = 0
39 RO Valve_status_4 WORD Digital Input #1
Register – Modbus
Register 12
Default = 0
40 RW Valve_status_5 WORD Digital Input #2
Register – Modbus
Register 13
Default = 0
Continued on next page