EasyManua.ls Logo

Fluke 1662 - Page 96

Fluke 1662
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical Installation Tester
Specifications
87
Earth Resistance Test (R
E
)
Models 1663 and 1664 only.
Range Resolution Accuracy
200 Ω 0.1 Ω ±(2 % + 5 digits)
2000 Ω 1 Ω ±(3.5 % + 10 digits)
Range: R
E
+ R
PROBE
[1]
Test Current
2200 Ω
3.5 mA
16000 Ω 500 μA
52000 Ω 150 μA
[1] Without external voltages
Frequency Output Voltage
128 Hz 25 V
Live Circuit Detection
Inhibits test if terminal voltage >10 V ac is
detected prior to start of test.
Auto Test Sequence
Models 1664 FC only.
Meets the specifications of the individual tests.