Manual Supplement 1736/1738 Users
3 7/19
Change #3, 594
On page 16, replace the Measurement Line Power Source
section with:
Measurement Line Power Source:
XWWarning
To prevent injury, do not touch the metal parts of one test lead
when the other is still connected to hazardous voltage.
WCaution
To prevent damage to the Product, make sure the measured voltage
does not exceed the input rating of the power supply.
1. Attach the power supply to the Logger.
2. Move the slide-cover on the power supply to access the safety
sockets.
3. Connect the short test leads (see Figure 7B & 7C) with t
he
po
wer supply inputs. Make sure to use the non-stackable plugs.
The test leads are rated for measurement/overvoltage CAT III
1000 V and CAT IV 600 V.
4. Connect the test leads with the voltage measurement inputs:
Connect A/L1 with one input of the power supply.
Connect N with the second input of the power supply.
OR
Connect A/L1 with one input of the power supply.
Connect B/L2 with the second input of the power supply.
5. Use the short fan out of the Voltage Test Lead, 3-phase + N.
Plug the connector A/L1 into the socket A/L1 of the voltage
measurement inputs of the Logger. Repeat this with B/L2, C/L3
and N.

Other manuals for Fluke 1736

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fluke 1736 and is the answer not in the manual?

Fluke 1736 Specifications

General IconGeneral
Product typeThree phase power measurement logger
Cable lock slot typeKensington
International Protection (IP) codeIP50
Operating altitude0 - 4000 m
Non-operating altitude0 - 12000 m
Storage temperature (T-T)-20 - 60 °C
Operating temperature (T-T)-10 - 50 °C
Operating relative humidity (H-H)10 - 95 %
Built-in displayYes
Display diagonal4.3 \
Touchscreen typeResistive
Display resolution480 x 272 pixels
Display technologyTFT
Efficiency68.2 %
Battery life4 h
Charging time6 h
Battery voltage3.7 V
Input frequency50/60 Hz
Battery capacity9.25 Wh
Power consumption (max)50 VA
Battery life (power save mode)5.5 h
Weight and Dimensions IconWeight and Dimensions
Depth55 mm
Width198 mm
Height167 mm
Weight1100 g
Power adapter weight400 g
Power supply dimensions (WxDxH)130 x 45 x 130 mm