EasyManua.ls Logo

Fluke 433 - Page 15

Fluke 433
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
2.2 Electrical Measurements 2
2-7
ACCURACY, RESOLUTION AND RANGE
Volt/Amps/Hertz Measurement Range Resolution Accuracy
Vrms(AC+DC)
Fluke 435
Fluke 433/434
1…600 Vrms
600…1000 Vrms
1…1000 Vrms
0.01 Vrms
0.01 Vrms
0.1 Vrms
± 0.1% of nominal
voltage
± 0.1%
± 0.5% of nominal
voltage
Vpk 1…1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor
(CF)
1.0 ... > 2.8 0.01 ± 5%
Arms (AC+DC)
Fluke 435
Fluke 433/434
Fluke 433/434 with i400s
Fluke 435 with I430flex
0…20.00 kArms
1
0…20.00 kArms
1
0…40 / 400 Arms
30…3000 Arms
0,001…10 Arms
1
0,001…10 Arms
1
0.1 and 1 Arms
1 Arms
± 0.5% ± 5 counts
3
± 1% ± 5 counts
3
± 1% ± 5 counts
3
± 0.5% ± 20 counts
3
Apk using 1mV/A scaling 0 - 5500 Apk 1A ± 5%
A Crest Factor (CF) 1 … 10 0.01 ± 5%
Hz
5
Fluke 435 @ 50Hz
nominal
Fluke 435 @ 60Hz
nominal
Fluke 433/434 @ 50Hz
nominal
Fluke 433/434 @ 60Hz
nominal
42.500 ... 57.500 Hz
51.000 ... 69.000 Hz
42.50 ... 57.50 Hz
51.00 ... 69.00 Hz
0.001 Hz
0.001 Hz
0.01 Hz
0.01 Hz
± 0.01Hz
± 0.01Hz
± 0.01Hz
± 0.01Hz
Dips and swells Measurement Range Resolution Accuracy
Vrms½ (AC+DC)
Fluke 435
Fluke 433/434
0.0% ….200% of
nominal voltage
0.0% ….200% of
nominal voltage
0.1Vrms
0.1Vrms
± 0.2% of nominal
voltage
± 1% of nominal voltage
Arms½ (AC+DC)
Fluke 435
Fluke 433/434
Fluke 433/434 with i400s
Fluke 435 with i430flex
0 … 20,000 Arms
1
0 … 20,000 Arms
1
0 … 400 Arms
30 … 3000 Arms
0,001 Arms…10 Arms
0,001 Arms…10 Arms
0.1 Arms and 1 Arms
1 Arms
± 1% ± 10 counts
3
± 2% ± 10 counts
3
± 2% ± 10 counts
3
± 1% ± 20 counts
3
Threshold levels Programmable thresholds in percent of nominal voltage
Event detection based upon ½cycle rms voltages
Captures Dips, Swells Interruptions and Rapid Voltage Changes
Duration hhh,mm,ss,mmm Half cycle One cycle

Related product manuals