Technical Data
Fluke 902
True-rms HVAC Clamp Meter
Use the Fluke 902 to:
•
Capture flue gas temperatures
•
Conduct flame rod testing
•
Measure start and run motor capacitors
•
Measure performance of variable frequency drives
Features include:
•
Capacitance
•
DC current to 200 uA
•
Contact temperature (K-type thermocouple)
•
True-rms
•
Min/Max
•
Hold
Heating, ventilation, air conditioning (HVAC)
technicians require a service tool that can
consistently keep up with their demands.
The Fluke 902 expands the existing line of
quality Fluke clamp meters by delivering the
features necessary to diagnose and repair
HVAC systems. Combined with True RMS
technology and a CAT III 600 V rating, the
Fluke 902 helps technicians do their jobs
safely and accurately.
Specifications
Feature Range Accuracy
Voltage dc 0 to 600.0 V 1 % ± 5 counts
Voltage ac
(true-rms)
0 to 600.0 V 1 % ± 5 counts (50/60 Hz)
Current ac
(true-rms)
0 to 600.0 A 2.0 % ± 5 counts (50/60 Hz)
Current dc 0 to 200.0 µA 1.0 % ± 5 counts
Resistance
0 to 9999
W
1.5 % ± 5 counts
Continuity
<= 30
W
Temperature*
(Type-K
thermocouple)
-10 °C to 400 °C
(-14 °F to 752 °F)
-40 °C to -10 °C
(-40 °F to -14 °F)
± 1.0 % + 0.8 °C
(± 1.0 % + 1.5 °F) typical
± 5.0 % + 1.5 °C
(± 5.0 % + 3.3 °F) typical
Capacitance 1 µF to 1000 µF 1.9 % ± 2 counts
Warranty Three-years
*Error does not include Type-K thermocouple errors