6. Technical specifications
5. Storage and maintenance
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been
exceeded, the batteries must be replaced. In this case, please contact your dealer or service center.
Storage
Charge the UPS for at least 5 hours before storing the unit. Cover the UPS, and place it upright in a cool, dry location.
During storage, recharge the battery in accordance with the following table:
Batteries must not be discarded as regular household waste! As part of the
company’s eco-friendly approach, we encourage you to follow all applicable local
waste regulations to dispose of your used devices and batteries properly.
Storage temperature Recharge frequency Runtime
-25°C - 40°C
40°C - 45°C
Every 3 months
Every 2 months
1-2 hours
1-2 hours
MPN FDC-1002T-A FDC-2002T-A
General
Capacity
Topology
Input
Nominal voltage
Voltage range (low line transfer)
Voltage range (low line comeback)
Voltage range (high line transfer)
Voltage range (high line comeback)
Frequency
Power factor
Total harmonic distortion (THDi)
AC plug style
Output
Nominal voltage
AC voltage regulation (battery mode)
Frequency (synchronized range)
Frequency (battery mode)
Power factor
Efficiency (AC mode)
Efficiency (battery mode)
1000VA/800W 2000VA/1600W
Double conversion
200-240VAC
160VAC / 140VAC / 120VAC / 110VAC ± 5%
(based on load percentage 100%-80% / 80%-70% / 70%-60% /
60%-0%)
Low line transfer voltage +15V
300VAC ± 5%
High line transfer voltage -10V
40-70Hz
≥0.99 at 100% load
≤15% at 100% load THDU <1.6%
IEC C14
200/208/220/230/240VAC
± 1%
47-53Hz at 50Hz system / 57-63Hz at 60Hz system
50Hz ± 0.1Hz or 60Hz ± 0.1Hz
0.8
≥88%
≥83%
105%-110%: 10min / 110%-130%: 1min / >130%: 3sec
0ms
4ms
3:1 (max)
≤3% THD (linear load) / ≤6% THD (non-linear load)
Pure sine wave
4 (Argentina Type I)
12V / 9Ah (2) 12V / 9Ah (4)
4 hours to 90% capacity
1A ± 10% (max)
27.4VDC ± 1% 54.7VDC ± 1%
Graphical LCD with blue backlight
Battery mode: Sounds every 4 seconds
Low battery: Sounds every second
Overload: Sounds every 0.5 second
Fault: Continuous sound
SNMP, RS-232, USB
ForzaTracker
32°F-104°F
UPS: -4°F-122°F
20-90% non-condensing
<1000m
Every 100m above 1000m decreases output power 1% up to 4000m
<50dB at 1 meter
5.7x8.7x11.1in 5.7x8.7x15.6in
22lb 38lb
Three years*
* Limited to two years on batteries