What to do if my Franklin Electric SubDrive150 shows high pressure?
- RRoy KingJul 26, 2025
If your Franklin Electric Controller is showing high pressure, first adjust the pressure sensor. If that doesn't work, disconnect the sensor wire at the PCB. If the drive continues to run, you will need to replace the drive. Also, verify the condition of the sensor wire; repair or replace it if necessary. The issue may be due to the pressure sensor setting or a shorted sensor wire.