EasyManua.ls Logo

FRC InControl TGA100 - Install Pressure Sensors; Figure 3. Pressure Sensors

FRC InControl TGA100
35 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TGA100 Rev0106
11
Install Pressure Sensors
The two pressure sensors are mounted on the discharge and intake manifolds of
the pump. If there is a check valve in the discharge side of the pump, mount the
discharge transducer before the check valve. T-fittings can be used to mount the pressure
transducers.
Note: Install the pressure sensor upright so water in the end of the pressure
transducer is able to drain back into the pipe.
1. Screw the sensor into a 1/4-18 NPT hole.
Caution: Do not use the main body that houses the electronics to tighten the
pressure sensor. Damage to the transducer may occur.
2. Tighten the sensor with a 9/16-inch (3/4 for alternate part) wrench on the lower
hex fitting.
3. Connect the pressure sensor cable from the control module to the pressure
sensor. (Refer to Wiring section.)
Caution: Do not use the main body
that houses the electronics to tighten
the sensor. Damage to the sensor
may occur.
Figure 3. Pressure Sensors
Intake - XE-IO3100PT2
Discharge - XE-FP4000PT1
1/4-18 NPT
1234567890
1234567890
1234567890
1234567890
1234567890
1234567890
1234567890
1234567890
1234567890
1234567890
1234567890
Lower Hex
Fitting
Main Body
1.02"
0.86"
0.80"
0.53"
0.78"
1.12"
Green Red
Note: The dimensions of the pressure sensors will be changing on or about
01April06. (Reference PCN0601-01.)
Supply
Voltage
5 VDC
Output
Signal
Ground
1.04"
1.06"

Related product manuals