ANALOG BOARD SETTINGS
COMMUNICATIONS
The following table is to be used when conguring the Quantum™ for external communications.
LK1
In 120 ohm long communications line termination.
Out * No termination.
* default setting
MISCELLANEOUS
LK2
In
Not Used
Out *
LK3
In
Not Used
Out *
LK4
In
Not Used
Out *
* default setting
NOTE: Although LK2, 3 and 4 are not used, they must still be set for the default positions.
DIPSWITCH SETTINGS
The following table is to be used to set the analog board addresses. Refer to and study the diagram at the bottom of this page
to determine the correct board conguration.
Comm. 4 of Quantum™ (Zones 1-15) Comm. 3 of Quantum™ (Zones 16-30)
I/O
Group
Analog
Board
#
SW
1
SW
2
SW
3
SW
4
SW
5
SW
6
SW
7
SW
8
I/O
Group
Analog
Board
#
SW
1
SW
2
SW
3
SW
4
SW
5
SW
6
SW
7
SW
8
1 1 Off Off Off Off Off Off Off Off 1 1 Off Off Off Off Off Off Off Off
2 2 On Off Off Off Off Off Off Off 2 2 On Off Off Off Off Off Off Off
3 3 Off On Off Off Off Off Off Off 3 3 Off On Off Off Off Off Off Off
4 4 On On Off Off Off Off Off Off 4 4 On On Off Off Off Off Off Off
5 5 Off Off On Off Off Off Off Off 5 5 Off Off On Off Off Off Off Off
Quantum™ LX
Control Board
I/O Group 1
Zones 16, 17, 18
I/O Group 2
Zones 19, 20, 21
I/O Group 3
Zones 22, 23, 24
I/O Group 4
Zones 25, 26, 27
I/O Group 5
Zones 28, 29, 30
I/O Group 1
Zones 1, 2, 3
I/O Group 2
Zones 4, 5, 6
I/O Group 3
Zones 7, 8, 9
I/O Group 4
Zones 10, 11, 12
I/O Group 5
Zones 13, 14, 15