SPECIFICATIONS
Capacities and Selection Data
Floating Air Pro / Premier Cooling Extended Capacity (By System Model)
System Model
Outdoor Air
Temp. (°F DB)
Indoor Air Temp. °F DB / °F WB
80 /67
TC SHC PI
kBtu/h kW
FPHW091/A
‑5 ‑7 4.95 1.14
5 3 5.45 1.07
14 12 7.08 1.17
17 15 8.93 1.30
23 19 9.67 1.30
32 28 9.65 1.19
35 33 9.89 1.03
47 43 10.54 0.94
59 50 9.86 0.82
FPHW121/A
‑5 ‑7 6.40 1.22
5 3 8.12 1.30
14 12 9.76 1.49
17 15 12.13 1.63
23 19 12.95 1.68
32 28 13.07 1.48
35 33 14.00 1.43
47 43 15.50 1.45
59 50 12.73 0.91
FPHW093/A
‑5 ‑7 4.95 1.14
5 3 6.20 1.20
14 12 7.29 1.27
17 15 8.59 1.34
23 19 9.33 1.38
32 28 9.85 1.34
35 33 10.23 1.19
47 43 11.65 1.11
59 50 10.78 0.80
FPHW123/A
‑5 ‑7 8.67 1.29
5 3 10.18 1.34
14 12 11.40 1.44
17 15 12.10 1.48
23 19 12.72 1.54
32 28 13.46 1.56
35 33 13.94 1.51
47 43 14.19 1.31
59 50 14.01 1.10

Table of Contents