61 PB
TROUBLESHOOTING
Malfunction Analysis
Malfunction Possible Reasons How to solve
"E4 indoor air outlet temperature sen-
sor failure/air blow out over
heat in electric heat mode"
"Indoor air outlet temperature sensor
open circuit or short circuit;
Indoor lter gets dirty or something
blocks the air intake."
"Check the sensor connection. If the
sensor is broken, replace with a new
one.Clean the lter and clean the air
way." See gures 703 and 704.
E5 Outdoor coil temperature sensor
failure.
Outdoor coil temperature sensor open
circuit or short circuit
Check the sensor connection. If the
sensor broken, replace with a new one.
See gure 703.
E8 Overheat protection/defrosting "Indoor fan failure/dirty lter/refrig-
erating system failure/indoor coil
temperature sensor failure"
Check the indoor fan/clean lter/rell
refrigerant/replace indoor coil sensor.
See gure 705 -710
E9 High pressure protection. "Outdoor fan failure/refrigerating sys-
tem failure/high pressure switch fail-
ure/outdoor coil temp sensor broken"
"Check outdoor fan/refrigerating pipe
system/high pressure switch/outdoor
coil temp sensor."