EasyManuals Logo

Friedrich WallMaster WS12C10 User Manual

Friedrich WallMaster WS12C10
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
38
HEAT PUMP TROUBLESHOOTING
Possible Solution
Possible Solution
esuaC elbissoP melborP
Unit cools when
heat is called for
Incorrect wiring Refer to applicable wiring diagram
Defective solenoid coil Check for continuity of coil
Reversing valve fails to shift
Block condenser coil & switch unit to cooling.
Allow pressure to build up in system, then
switch to heating. If valve fails to shift, replace
valve.
Defective electronic control board Replace electronic control board
esuaC elbissoP melborP
Heating
insuf cient
Heating capillary tube partially
restricted
Check for partially starved outer coil. Replace
heating capillary tube
Check valve leaking internally
Switch unit several times from heating to
cooling. Check temperature rise across
coil. Refer to speci cation sheet for correct
temperature rise
Reversing valve failing to shift
completely; bypassing hot gas
Deenergize solenoid coil, raise head pressure,
energize solenoid to break loose. If valve fails
to make complete shift, replace valve.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Friedrich WallMaster WS12C10 and is the answer not in the manual?

Friedrich WallMaster WS12C10 Specifications

General IconGeneral
BrandFriedrich
ModelWallMaster WS12C10
CategoryAir Conditioner
LanguageEnglish

Related product manuals