◆Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration,
sharp edges, or any other adverse environmental effects. The check shall also take into
account the effects of aging or continual vibration from sources such as compressors or
fans.
◆Before carrying out Decommissioning procedure, it is essential that the technician is
completely familiar with the equipment and all its detail. It is recommended good practice
that all refrigerants are recovered safely. Prior to the task being carried out, an oil and
refrigerant sample shall be taken in case analysis is required prior to re- use of recovered
refrigerant. It is essential that electrical power is available before the task is commenced.
◆When removing refrigerant from a system, either for servicing or decommissioning, it is
recommended good practice that all refrigerants are removed safely.
◆
The recovery equipment shall be in good working order with a set of instructions
concerning the equipment that is at hand and shall be suitable for the recovery of all
appropriate refrigerants including, when applicable, FLAMMABLE REFRIGERANTS.
◆
The recovered refrigerant shall be returned to the refrigerant supplier in the correct
recovery cylinder, and the relevant waste transfer note arranged. Do not mix refrigerants
inrecovery units and especially not in cylinders.
Warning: Risk of fire / flammable materials, taking care to avoid causing a fire by igniting
flammable material.
The maximum loading of each type of shelf is 8kg.
The ambient temperature and humidity conditions of the show case climate class
following the tab below
Water vapour
mass in dry air
g/kg
NOTE the water vapour mass dry air is one of the main points influencing the performance
and the energy consumption of the cabinets. Therefore, the order of the climate class in the
table is based on the water vapour mass column. See also Annex B to compare lab and store
conditions.