128
Display during normal operation
When there is an error in one of the power
stage sets, the display flashes between
"STATE" and the corresponding status
code
(e.g., "STATE 515")
and
"ENTER"
- Press the "Enter" key twice
- The status display of the power stage
sets "STATE PS" appears
- Press the "Enter" key
Class 1 Status
Codes
Class 1 status codes are typically tempora-
ry. Their cause lies in the public grid.
The initial response of the inverter is to disconnect itself from the grid. The grid is subse-
quently checked for the stipulated monitoring period. If after the end of this period no fur-
ther defect is identified, your inverter resumes operating and feeding power into the grid.
IMPORTANT! The 2nd position x defines the exact network point for the following status
codes:
0 = several / all 3 phases
1 = L1
2 = L2
3 = L3