13
EN-US
Finally...
Insert the inductance bridge (1)
Connect fan cable (3, 4)
Connect 6 cables (2, 5, 6, 7, 8, and 9)
Secure inductance bridge (1) with 4 TX 25 screws (10)
tightening torque: 3 Nm / 2.2 ft lb.
Close power stage set cover
Secure cover to the power stage set with TX 25 side screws
tightening toque 3 Nm / 2.2 ft lb.
Turn on DC main switch
If available, turn on the external AC and DC disconnecter
IMPORTANT! Neatly run the fan cables in the guide on the right side.
CAUTION! An inadequate grounding conductor connection can cause serious in-
juries to persons and damage to (or loss of) property. The housing screws provide
an adequate grounding conductor connection for the housing ground and should
not be replaced under any circumstances by other screws that do not provide a
proper grounding conductor connection.
(2) (3) (4) (5)(1)
(9) (8) (7) (6)
(10)
(10)
(10)
(10)