Correct routing of
the mains/char-
ging cables
CAUTION!
Danger due to overheating as a result of incorrectly laid mains/charging cables.
Risk of damage to the components.
Lay the mains/charging cable without a loop.
Do not cover the mains/charging cable.
Charging cables longer than 5 m (16 ft. 4.85 in.) must be laid individually (no bund-
ling).
For charging cables longer than 5 m (16 ft. 4.85 in.), a maximum ambient temperat-
ure of 30 °C (86 °F) must not be exceeded.
The mains/charging cable may only be replaced by a qualified electrician.
Charging cables longer than 5 m (16 ft. 4.85 in.) can have an increased surface tem-
perature (be aware of hot surfaces).