Operating coil characteristics
z AC-operated type
Type
FJ-B06 FJ-B09 FJ-B12 FJ-B18 FJ-B25 FJ-B32 FJ-B40 FJ-B50 FJ-B65 FJ-B80 FJ-B95
Pick-up voltage range
(AC220/230V, 50Hz)
Making voltage [V]
120-152 120-152 120-152 126-150 126-150 126-150 120-150 120-150 120-150 126-150 126-150
Drop-out voltage [V]
73-95 73-95 73-95 84-118 84-118 84-118 90-120 90-120 90-120 90-130 90-130
Power consumption Inrush [VA]
22 22 22 90 90 90 120 120 120 180 180
Sealed [VA]
4.5 4.5 4.5 9 9 9 12.7 12.7 12.7 13.3 13.3
Loss Sealed [W]
1.5 1.5 1.5 2.7 2.7 2.7 3.6 3.6 3.6 4.5 4.5
Operating
times
Coil ON Contact ON [ms]
9-20 9-20 9-20 9-20 9-20 9-20 10-17 10-17 10-17 10-18 10-18
Coil OFF Contact OFF [ms]
5-15 5-15 5-15 4-20 4-20 4-20 6-13 6-13 6-13 8-18 8-18
z
DC-operated type
Type
FJ-B06/G FJ-B09/G FJ-B12/G FJ-B18/G FJ-B25/G FJ-B32/G
Pick-up voltage range
(DC24V)
Making voltage [V]
8-14 8-14 8-14 10-15 10-15 10-15
Drop-out voltage [V]
3-6 3-6 3-6 3-7 3-7 3-7
Power consumption Inrush [VA]
2.4 2.4 2.4 7 7 7
Sealed [VA]
2.4 2.4 2.4 7 7 7
Time constant Sealed [W]
20 20 20 50 50 50
Operating
times
Coil ON Contact ON [ms]
17-30 17-30 17-30 43-47 43-47 43-47
Coil OFF Contact OFF [ms]
5-15 5-15 5-15 10-24 10-24 10-24
Performance
Frame size 06 09 12 18 25 32 40 50 65 80 95
Type
AC-operated type
FJ-B06 FJ-B09 FJ-B12 FJ-B18 FJ-B25 FJ-B32 FJ-B40 FJ-B50 FJ-B65 FJ-B80 FJ-B95
DC-operated type
FJ-B06/G FJ-B09/G FJ-B12/G FJ-B18/G FJ-B25/G FJ-B32/G
– – – – –
Rated insulation voltage Ui [V] 690 1000
Rated impulse voltage Uimp[kV] 6 8
Main
circuit
Making
current [A]
220/230V 60 90 120 180 250 320 400 500 650 800 950
380/400V 60 90 120 180 250 320 400 500 650 800 950
Breaking
current [A]
220/230V 48 72 96 144 200 256 320 400 520 640 760
380/400V 48 72 96 144 200 256 320 400 520 640 760
Operating cycles per hour AC-3 [times/hour]
1200 1200 1200 1200 1200 1200 600 600 600 600 600
FJ Series
Operating coil characteristics
Information subject to change without notice
13
Contactors and Thermal Overload Relays
FJ Series