Main circuit ratings
z In accordance with the ratings of the IEC and GB standards (IEC60947-4-1 and GB14048.4)
Applicable
Type
Max. motor capacity [kW] Operational current Ie[A]
Conventional free
air thermal current
(Rated thermal
current) [A]
Three-phase squirrel-cage motor (AC-3) Three-phase squirrel-cage motor (AC-3)
Resistive load
(AC-1)
220/230V 380/400V 600/690V 220/230V 380/400V 600/690V Below 400V
FJ-B06 1.5 2.2 2.7 6 6 3 20 20
FJ-B09 2.2 4 4 9 9 5 20 20
FJ-B12 3 5.5 5.5 12 12 6 20 20
FJ-B18 4 7.5 7.5 18 18 7 25 25
FJ-B25 5.5 11 7.5 25 25 9 32 32
FJ-B32 7.5 15 7.5 32 32 10 40 40
FJ-B40 11 18.5 11 40 40 15 50 50
FJ-B50 15 22 15 50 50 19 60 60
FJ-B65 18.5 30 22 65 65 26 65 65
FJ-B80 22 40 30 80 80 38 100 100
FJ-B95 25 45 37 95 95 44 105 105
Auxiliary circuit ratings
z In accordance with the ratings of the IEC and GB standards (IEC60947-5-1 and GB14048.5)
Type
Conventional free
air thermal current
(Rated thermal
current) [A]
Making and
breaking
current (AC)
[A]
Rated operational current [A]
Minimum
operating
voltage and
current *
1
AC DC
Rated
operating
voltage [V]
AC-15
(Inductive
load)
AC-12
(Resistive
load)
Rated
operating
voltage [V]
DC-13 *
2
(Inductive
load)
DC-12
(Resistive
load)
FJ-B06
to
FJ-B12
10 60 110V 6 10 24V 3 5
DC24V, 10mA
30 220/230V 3 8 48V 1.5 3
15 380/400V 1.5 5 110V 0.55 2.5
12 500/600V 1.2 5 220V 0.27 1
FJ-B18
to
FJ-B95
10 60 110V 6 10 24V 3 5
DC5V, 3mA
30 220/230V 3 8 48V 1.5 3
15 380/400V 1.5 5 110V 0.55 2.5
12 500/600V 1.2 5 220V 0.27 1
*
1
The failure level is 10-7 for a normal environment without dust, dirt, or corrosive gas.
*
2
Given the time constant L/R = 70ms
FJ Series
Ratings
Information subject to change without notice
12
Contactors and Thermal Overload Relays