Features
• The smallest one in the basic type series (6A, 9A, 12A rated
products)
• 6A, 9A and 12A rated products are small sized AC contactors of
AC and DC coil products with the same outline dimensions.
• DC coil products are low-power-consumption products that can be
driven directly by PLC. (FJ-B06/G to B12/G type DC24V coil)
• Energy-saving type with an energy efciency level of 2.
(6A, 9A, 12A, 40A to 95A rated products)
Types and ratings
z Standard-type (non-reversing)
Frame Max. motor capacity (kW)
AC-3, IEC60947-4-1
Operational current (A) Operational
current (A)
AC-1
Conventional
free air thermal
current (A)
Auxiliary
contact
arrangement
Type
AC
operated
DC
operated
200/240V 380/440V 600/690V 200/240V 380/440V 600/690V Under 440V
06 1.5 2.2 2.7 6 6 3 20 20
1NO or 1NC
FJ-B06 FJ-B06/G
09 2.2 4 4 9 9 5 20 20
1NO or 1NC
FJ-B09 FJ-B09/G
12 3 5.5 5.5 12 12 6 20 20
1NO or 1NC
FJ-B12 FJ-B12/G
18 4 7.5 7.5 18 18 7 25 25
1NO or 1NC
FJ-B18 FJ-B18/G
25 5.5 11 7.5 25 25 9 32 32
1NO or 1NC
FJ-B25 FJ-B25/G
32 7.5 15 7.5 32 32 10 40 40
1NO or 1NC
FJ-B32 FJ-B32/G
40 11 18.5 11 40 40 15 50 50 1NO1NC FJ-B40 –
50 15 22 15 50 50 19 60 60 1NO1NC FJ-B50 –
65 18.5 30 22 65 65 26 65 65 1NO1NC FJ-B65 –
80 22 40 30 80 80 38 100 100 1NO1NC FJ-B80 –
95 25 45 37 95 95 44 105 105 1NO1NC FJ-B95 –
(Note 1) The rated values meet the standards IEC60947-4-1 and GB14048.4.
z Reversing-type
Frame Max. motor capacity (kW)
AC-3, IEC60947-4-1
Operational current (A) Operational
current (A)
AC-
1
Conventional
free air thermal
current (A)
Auxiliary
contact
arrangement
*1
Type
AC
operated
DC
operated
200/240V 380/440V 600/690V 200/240V 380/440V 600/690V Under 440V
06 1.5 2.2 2.7 6 6 3 20 20
1NC×2
or
1NO×2
*2
FJ-B06RM
FJ-B06RM/G
09 2.2 4 4 9 9 5 20 20 FJ-B09RM
FJ-B09RM/G
12 3 5.5 5.5 12 12 6 20 20 FJ-B12RM
FJ-B12RM/G
18 4 7.5 7.5 18 18 7 25 25 FJ-B18RM
FJ-B18RM/G
25 5.5 11 7.5 25 25 9 32 32 FJ-B25RM
FJ-B25RM/G
32 7.5 15 7.5 32 32 10 40 40 FJ-B32RM
FJ-B32RM/G
(Note 1) The rated values meet the standards IEC60947-4-1 and GB14048.4.
*1 In the auxiliary contact arrangement, "1NC" indicates the number of contacts of 1 AC contactor, while "×2" means the total values of 2 contactors. Please make
orders according to the codes of the auxiliary contacts of each piece of equipment.
*2 Auxiliary contact 1NO×2 is available on request. However, these contactors are not electrically interlocked. Be sure to arrange electrical interlock circuit externally to
avoid short-circuit accidents.
FJ-B12 FJ-B65
Magnetic contactors
FJ Series
Ordering information (Types)
z Reversing magnetic contactor (FJ-B18RM Coil AC220/230V 50Hz when the auxiliary contact is 1NC×2)
FJ-B12 S N5 10
(1) Type
(3) Coil voltage code
(4) Contact arrangement
(auxiliary contact 1NC×2: 01 Auxiliary contact 1NO×2: 10)
Please refer to Type number nomenclature in P10
(2)
Built-in coil surge
Blank: None
S: Buit-in
Information subject to change without notice
15
Contactors and Thermal Overload Relays
FJ Series