EasyManua.ls Logo

Fuji Electric FJ Series - Page 9

Fuji Electric FJ Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
z Magnetic contactors
Series FJ Series
Frame 06 09 12
18 25 32
40 50 65 80 95
Appearance
Type AC operated type FJ-B06 FJ-B09 FJ-B12
FJ-B18 FJ-B25 FJ-B32
FJ-B40 FJ-B50 FJ-B65 FJ-B80 FJ-B95
DC operated type FJ-B06/G FJ-B09/G FJ-B12/G
FJ-B18/G FJ-B25/G FJ-B32/G
Max. motor capacity (kW)
AC-3, IEC60947-4-1
200/240V 1.5kW 2.2kW 3kW
4kW 5.5kW 7.5kW
11kW 15kW 18.5kW 22kW 25kW
380/440V 2.2kW 4kW 5.5kW
7.5kW 11kW 15kW
18.5kW 22kW 30kW 40kW 45kW
600/690V 2.7kW 4kW 5.5kW
7.5kW 7.5kW 7.5kW
11kW 15kW 22kW 30kW 37kW
Operational current (A) 200/240V 6A 9A 12A
18A 25A 32A
40A 50A 65A 80A 95A
380/440V 6A 9A 12A
18A 25A 32A
40A 50A 65A 80A 95A
600/690V 3A 5A 6A
7A 9A 10A
15A 19A 26A 38A 44A
Conventional free air thermal current (rated thermal current) Ith (A) 20A 20A 20A
25A 32A 40A
50A 60A 65A 100A 105A
Auxiliary contact arrangement 1NO or 1NC 1NO or 1NC 1NO or 1NC
1NO or 1NC 1NO or 1NC 1NO or 1NC
1NO1NC 1NO1NC 1NO1NC 1NO1NC 1NO1NC
Dimensions
W × H × D (mm)
AC operated type 45 × 48 × 49
43 × 81 × 80 53 × 81 × 81
63.5 × 90 × 96 63.5 × 90 × 96 63.5 × 90 × 96
76.5 × 110 × 111 76.5 × 110 × 111
DC operated type
43 × 81 × 107 53 × 81 × 108
Optional unit Auxiliary contact block Front mounting SZ1FA11 or SZ1FA11H, SZ1KA,SZ1KAH
SZ-A (2pole or 4pole)
Side mounting
SZ-AS1
Coil surge suppression unit
*1
SZ-Z1 to Z9
SZ-Z31 to Z35
Standards
s
s
Note: *1. Attach “S” behind the built-in order model of coil surge suppression unit.
z Thermal overload relays
Type TK12B- TK18B- TK32B- TK65B- TK95B-
Appearance
Protection function Overload Overload Overload Overload Overload
Tripping class 10A 10A 10A 10A 10A
Ampere setting range (A) / code 0.1-0.15 [P10]
0.13-0.2 [P13]
0.18-0.27 [P18]
0.24-0.36 [P24]
0.34-0.52 [P34]
0.48-0.72 [P48]
0.64-0.96 [P64]
0.8-1.2 [P80]
0.95-1.45 [P95]
1.4-2.1 [1P4]
1.7-2.6 [1P7]
2.2-3.4 [2P2]
2.8-4.2 [2P8]
4-6 [004]
5-7.5 [005]
6-9 [006]
7-10.5 [007]
9-13 [009]
0.1-0.15 [P10]
0.13-0.2 [P13]
0.18-0.27 [P18]
0.24-0.36 [P24]
0.34-0.52 [P34]
0.48-0.72 [P48]
0.64-0.96 [P64]
0.8-1.2 [P80]
0.95-1.45 [P95]
1.4-2.1 [1P4]
1.7-2.6 [1P7]
2.2-3.4 [2P2]
2.8-4.2 [2P8]
4-6 [004]
5-7.5 [005]
6-9 [006]
7-10.5 [007]
9-13 [009]
13-18 [013]
0.1-0.15 [P10]
0.13-0.2 [P13]
0.18-0.27 [P18]
0.24-0.36 [P24]
0.34-0.52 [P34]
0.48-0.72 [P48]
0.64-0.96 [P64]
0.8-1.2 [P80]
0.95-1.45 [P95]
1.4-2.1 [1P4]
1.7-2.6 [1P7]
2.2-3.4 [2P2]
2.8-4.2 [2P8]
4-6 [004]
5-7.5 [005]
6-9 [006]
7-10.5 [007]
9-13 [009]
12-18 [012]
16-22 [016]
20-26 [020]
26-32 [026]
4-6 [004]
5-8 [005]
6-9 [006]
7-11 [007]
9-13 [009]
12-18 [012]
18-26 [018]
24-36 [024]
32-42 [032]
40-50 [040]
44-54 [044]
53-65 [053]
7-11 [007]
9-13 [009]
12-18 [012]
18-26 [018]
24-36 [024]
28-40 [028]
34-50 [034]
45-65 [045]
48-68 [048]
64-80 [064]
68-86 [068]
86-96 [086]
Applicable contactors
FJ-B06, B09, B12
FJ-B18 FJ-B25, B32
FJ-B40, B50, B65 FJ-B80, B95
Dimensions W × H × D (mm)
45 × 49.5 × 50
45 × 48.5 × 61 53 × 50.5 × 61 54 × 78.5 × 97 68 × 89.5 × 102.5
Note: Replace the mark in the type number by the Ampere setting range code.
Information subject to change without notice