(F codes continued)
Code Name Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Defaul
t
setting
F37
Load Selection/Auto
Torque Boost
0: Variable torque load
1: Constant torque load
2: Auto-torque boost
N Y 1
F39
Stop Frequency
(Holding Time)
0.00 to 10.00
0.01 s Y Y 0.00
F42
Control Mode
Selection 1
0: V/f control with slip compensation inactive
1: Dynamic torque vector control
2: V/f control with slip compensation active
N Y 0
F43
Current Limiter
(Mode selection)
0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during ACC/DEC)
2: Enable during ACC/constant speed operation
Y Y 2
F44
(Level)
20 to 180 : 3.7 kW(5HP)
(The data is interpreted as the rated output current of
the inverter for 100%.) *2
1 % Y Y 160
F50
Electronic Thermal
Overload Protection
for Braking Resistor
(Discharging
capability)
1 to 900, OFF (Cancel)
1 kWs Y
Y1
Y2
OFF
F51
(Allowable average
loss)
0.001 to 50.00
0.001 kW Y
Y1
Y2
0.001
*1 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can
display.(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*2 The percentage is relative to the rated output current.