Instruction Manual
High Performance Compact Inverter
Thank you for purchasing our FRENIC-Multi series of inverters.
This product is designed to drive a three-phase induction motor. Read through this instruction
manual and be familiar with the handling procedure for correct use.
Improper handling might result in incorrect operation, a short life, or even a failure of this
product as well as the motor.
Deliver this manual to the end user of this product. Keep this manual in a safe place until this
product is discarded.
For how to use an optional device, refer to the instruction and installation manuals for that
optional device.
Fuji Electric FA Components & Systems Co., Ltd. INR-SI47-1204-E
Fuji Electric Corp. of America

Table of Contents

Other manuals for Fuji Electric FRENIC-Multi

Questions and Answers

  • D
    Dr. Dillon BellJul 30, 2025
    What to do if my Fuji Electric FRENIC-Multi Inverter shows an enable circuit failure?
    • M
      Melissa LucasJul 30, 2025
      If your Fuji Electric Inverter shows an enable circuit failure, first ensure the interface PCB is correctly mounted. If that's not the issue, check that the safety switch output levels (EN1/EN2) are consistent (both High/High or Low/Low). Power cycle the inverter to clear the alarm. If the problem persists and a single enable circuit failure is detected, the inverter requires repair; contact your Fuji Electric representative, as the 'Reset alarm' terminal command RST won't resolve it.
  • B
    bbentleyAug 5, 2025
    Why does my Fuji Electric FRENIC-Multi Inverter show overheat protection?
    • B
      Brian YatesAug 5, 2025
      The Fuji Electric Inverter might show overheat protection because the heat sink temperature is too high. This can happen if the inverter fan isn't working or if the inverter is overloaded.
  • P
    Penny LoweAug 9, 2025
    What causes undervoltage protection in Fuji Electric Inverter?
    • R
      Robin ReedAug 10, 2025
      Undervoltage protection in Fuji Electric Inverters is activated when the voltage in the DC link is too low (200 V for 200 V class inverters; 400 V for 400 V class inverters). Note: if F14=4 or 5, this alarm won't activate when the DC link voltage is low.
  • D
    Devin TravisAug 15, 2025
    What does electronic thermal overload motor 1 mean on a Fuji Electric FRENIC-Multi Inverter?
    • S
      smithtimothyAug 15, 2025
      The 'Electronic thermal overload motor 1' message on your Fuji Electric Inverter indicates that the inverter is protecting the motor according to the electronic thermal overload protection settings. Specifically: - F10 (A06) =1 is for general purpose motors. - F10 (A06)=2 is for inverter motors. - F11 (A07) defines the operation level (current level). - F12 (A08) defines the thermal time constant. Note: F functions are for motor 1 and A functions are for motor 2.
  • J
    Julie AndersonAug 20, 2025
    What to do if PTC thermistor stops Fuji Electric Inverter?
    • F
      fmendozaAug 20, 2025
      If the PTC thermistor stops your Fuji Electric Inverter to protect the motor, ensure the thermistor is connected between terminals [C1] and [11]. Also, verify the slide switch position and that functions H26 (enable) and H27 (level) are correctly set.
  • D
    david51Aug 25, 2025
    What does external alarm input mean on Fuji Electric FRENIC-Multi?
    • H
      Haley JonesAug 26, 2025
      The 'External alarm input' on your Fuji Electric Inverter means that a digital input programmed with the function THR (9) has been deactivated.