2.3.3 Recommended wire sizes
Table 2.7 lists the recommended wire sizes. The recommended wire sizes for the main circuits are
examples of using HIV single wire for 75qC (167qF) at an ambient temperature of 50qC (122qF).
Table 2.7 Recommended Wire Sizes
Recommended wire size AWG(mm
2
)*
1
Main circuits
Main circuit
power input
[L1/R, L2/S, L3/T]
[L1/L, L2/N]
Power supply voltage
Nominal
applied
motor
Inverter type
w/ DCR w/o DCR
Ground-
ing
[
G]
Inverter
output
[U, V, W]
DCR
[P1,
P (+)]
Braking
resistor
[P(+),
DB]
Control
circuit
1/8 FRNF12E1䂓-2U
1/4 FRNF25E1䂓-2U
1/2 FRNF50E1䂓-2U
1 FRN001E1䂓-2U
2 FRN002E1䂓-2U
3 FRN003E1䂓-2U
5 FRN005E1䂓-2U
14
(2)
14
(2)
14
(2)
14
(2)
7.5 FRN007E1䂓-2U
14
(2)
11(3.5) 11(3.5) 11(3.5)
10 FRN010E1䂓-2U 11(3.5) 9(5.5)
11(3.5)
9(5.5)
15 FRN015E1䂓-2U 9(5.5) 5(14)
9(5.5)
8(8) 8(8)
Three-phase 230 V
20 FRN020E1䂓-2U 5(14) 3(22) 8(8) 5(14) 5(14)
14
(2)
20
(0.5)
to
16
(1.25)
1/2 FRNF50E1䂓-4U
1 FRN001E1䂓-4U
2 FRN002E1䂓-4U
3 FRN003E1䂓-4U
5 FRN005E1䂓-4U
7.5 FRN007E1䂓-4U
14
(2)
10 FRN010E1䂓-4U
14
(2)
14
(2)
15 FRN015E1䂓-4U
14
(2)
11(3.5)
14
(2)
11(3.5)
Three-phase 460 V
20 FRN020E1䂓-4U 11(3.5) 9(5.5)
11(3.5)
11(3.5) 9(5.5)
14
(2)
20
(0.5)
to
16
(1.25)
1/8 FRNF12E1䂓-7U
1/4 FRNF25E1䂓-7U
1/2 FRNF50E1䂓-7U
1 FRN001E1䂓-7U
2 FRN002E1䂓-7U
14
(2)
Three-phase
230 V
3 FRN003E1䂓-7U
14
(2)
11(3.5)
14
(2)
14
(2)
14
(2)
14
(2)
20
(0.5)
to
16
(1.25)
DCR: DC reactor
*
1
Use the terminal crimp with an insulation sheath or with processing by the insulation tube.
Use the insulated wire of 75qC (167qF), 600 V, HIV-insulated. This selection assumes the inverter is
used in ambient temperature at 50qC (122qF).
Note 1) A box (