32
It changes into the Rated Voltage display in pushing the SET button.
Push button/ button when you change the content display. The
content is changed when the SET button is pushed by the content that
changes and it moves to the next item display. Push the ESC button when
it returns to the Rated Voltage item.
6-1-6 Mode select
Figure 6-7 Mode select
It changes into the Mode select display in pushing the SET button.
Push button/ button when you change the content display. The
content is changed when the SET button is pushed by the content that
changes and it moves to the next item display. Push the ESC button when
it returns to the Mode select item.
・Normal mode is fixation in the mode of the On-Line.
・HE mode is fixation in the mode of the On-HE.
・Intelligent mode ijudges a utility input and does the transfering of On-Line
On-HE.
UPS transfers from On-Line to On-HE by the automatic operation. The
change from On-HE to On-Line, when the input deviates from the HE input
range, and when the input is bypass available transfers by automatic
operation. Moreover, when there is a mode transition by the communication,
it gives priority to the communication, dont automatic operation. However,
when the UPS changes into the OnBattery by the condition of the AC input,
the change operation is not done.
When the communication is not possible, or the communication is invalided ,
or newly communication is connected, or UPS shuts down, after the mode is
changed by the communication, UPS change to automatic operation.
CONF I GURAT I ON   
MOD E S E L EC T 
MOD E S E L EC T 
NORMAL MODE
MOD E S E L EC T 
HE MODE
MOD E S E L EC T 
INTELLIGENT MODE
Factory
Setting