Installation space requirement
1,500
or more
1,000 or more
1,800 or more
Obstruction
3,000 or more
Strong and durable ceiling
Floor
256 or more
Unit: mm
Maximum height from floor to ceiling (Unit: mm)
Mode AUYG30LRLE AUYG36LRLE AUYG45LRLA
Low 2,700
Standard 3,200
High ceiling 3,600 4,200
3-way direction setting:
100 or more*
Unit: mm
NOTES:
To set “3-direction”, optional Air outlet shutter plate (UTR-YDZB) must be installed, and the “out-
let-direction” need to be switched to “3-way” by remote controller.
*When installing the indoor unit, be careful about the maintenance space.
The ceiling height cannot be set in the 3-way outlet mode. Therefore, ceiling height setting
change by function setting 20 is prohibited. For details, refer to "Contents of function setting" on
page 284.