En-18
9.4. Checklist
Check description Check method Criteria
1
High and low pressure values
are normal.
Check it with a pres-
sure gauge.
Cooling: low pressure ap-
prox. 0.8 MPa
Heating: high pressure
approx.
3.0 MPa
2
Drain water is discharged
smoothly through the drain
hose.
Check it by pouring
water.
3
Indoor and outdoor unit fans
are operating.
Check them visually.
4
Compressor operates after the
indoor unit operates.
Check the operating
sound.
5
Difference between inlet and
outlet temperatures is normal.
Measure the inlet and
outlet temperatures.
Temperature difference
10 degrees
6 Error is not displayed.
Check the 7 segment
display.
Error blinking or no error
code display
10. LED STATUS
You can determine the operating status by the lighting up and blinking of the LED display.
Check the status using the table below.
10.1. Normal operation codes
Mode CODE DESCRIPTION
Operation
CL Cooling
Ht Heating
o r During oil recovery operation
d F During defrosting operation
P C During power saving operation
L n During low noise operation
10.2. Error codes
Mode CODE DESCRIPTION
Communica-
tion error
E 1 4. 2 Outdoor unit network communication 2 error
E 1 4. 5 The number of indoor unit shortage
Function setting
error
E 2 2. 1 Indoor unit capacity error
E 2 4. 2 Connection unit number error (Indoor unit)
E 2 6. 1 Indoor unit duplicate address error
E 2 8. 1 Auto address setting error
E 2 8. 4 Signal ampli er auto address error
Indoor unit
actuator error
E 5 U. 1 Indoor unit miscellaneous error
Outdoor unit
PCB/Electrical
component/
Switch error
E61.5Outdoor unit reverse/missing phase & wiring error
E 6 2. 3 Outdoor unit EEPROM access error
E 6 2. 6 Outdoor unit inverters communication error
E 6 2. 8 Outdoor unit EEPROM data corruption error
E 6 3. 1 Outdoor unit inverter error
E67.2
Outdoor unit inverter PCB power short interruption
error
E68.2
Outdoor unit rush current limiting resister temp. rise
error (protective operation)
E69.1
Outdoor unit transmission PCB parallel communica-
tion error
Outdoor unit
sensor error
E 7 1. 1 Outdoor unit discharge temp. thermistor 1 error
E72.1
Outdoor unit compressor temp. thermistor 1 error
E73.3
Outdoor unit heat ex. liquid temp. thermistor error
E 7 4. 1 Outside air temp. thermistor error
E 7 5. 1 Outdoor unit suction gas temp. thermistor error
E 7 7. 1 Outdoor unit heat sink temp. thermistor error
E82.1
Outdoor unit sub-cool heat ex. gas inlet temp. therm-
istor error
E82.2
Outdoor unit sub-cool heat ex. gas outlet temp.
thermistor error
E 8 3. 2 Outdoor unit liquid pipe temp. thermistor 2 error
E84.1
Outdoor unit current sensor 1 error
(permanent stop)
E 8 6. 1 Outdoor unit discharge pressure sensor error
E 8 6. 3 Outdoor unit suction pressure sensor error
E 8 6. 4 Outdoor unit high pressure switch 1 error
Outdoor unit
actuator error
E 9 3. 1 Outdoor unit inverter compressor start up error
E 9 4. 1 Outdoor unit trip detection
E95.5
Outdoor unit compressor motor loss of synchroniza-
tion
E 9 7. 1 Outdoor unit fan motor 1 lock error
E 9 7. 4 Outdoor unit fan motor 1 undervoltage error
E97.5
Outdoor unit fan motor 1 temperature error
(protective action)
E98.1Outdoor unit fan motor 2 lock error
E98.5
Outdoor unit fan motor 2 temperature error
(protective action)
E 9 A. 1 Outdoor unit coil 1 (expansion valve 1) error
E 9 A. 2 Outdoor unit coil 2 (expansion valve 2) error
Refrigerant
system error
EA1.1
Outdoor unit discharge temperature 1 error (perma-
nent stop)
EA3.1
Outdoor unit compressor 1 temperature error
E A 4. 1 Outdoor unit high pressure error
E A 4. 2 Outdoor unit high pressure protective action 1
E A 5. 1 Outdoor unit low pressure error
E A C. 4 Outdoor unit heat sink temperature error
7 segment LED indicator:
,
, , , , , ,
,
,
,
,
t:
L:
7:
H: J:
6:
A
:C:E:F:
, , ,
d: n: o: r:
,
,
,
,
,
9:
P:
U:
S:
8:
,
,
, ,
5:3: 4:
1: 2:
,
0:
11. INFORMATION
Main contents of label
Item Detail
1. Model name Model name
2. Serial number Serial number
3. Electric characteristics Phase, rated voltage, and frequency
4. Weight Product weight
5. Capacity
Cooling/heating capacity under cooling/heating
condition (refer to item 15)
6. Current
Electric current during cooling/heating operation
under cooling/heating condition (refer to item 15)
7. Input power
Input during cooling/heating operation under cool-
ing/heating condition (refer to item 15)
8. Max. Current
Maximum electric current (temperature condition is
max. cooling condition [refer to item 16])
9. Air circulation Air circulation
10. Noise level Noise level
11. Refrigerant Refrigerant type and initial charging amount
12. Max. pressure (HP/LP)
Means pressure of High Pressure side/Low Pres-
sure side
13. Protection Protection level against dust and water
14. Working temperature Working temperature
15. Condition of cooling/heating
Dry-bulb temperature and wet-bulb temperature
under standard cooling/heating condition
16. Condition of max. cooling
Dry-bulb temperature and wet-bulb temperature at
maximum electric current and input
17. Manufacture year Manufacture year
18. Origin Origin country
19. Manufacturer
Manufacturer
FUJITSU GENERAL LIMITED
Address: 3-3-17, Suenaga, Takatsu-ku, Kawasaki
213-8502, Japan
9380545163-02_IM.indb 189380545163-02_IM.indb 18 5/17/2018 14:56:225/17/2018 14:56:22

Related product manuals