En-14
7.4. Function setting
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address
settings.
•
Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
number
Setting number
De-
fault
Details
Filter indica-
tor interval
11
00
Standard
○
Adjust the fi lter cleaning interval notifi ca-
tion. If the notifi cation is too early, change
to setting 01. If the notifi cation is too late,
change to setting 02.
01 Longer
02 Shorter
Filter indica-
tor action
13
00 Enable
○
Enable or disable the fi lter indicator.
Setting 02 is for use with a central remote
controller.
01 Disable
02
Display only on
central remote
controller
Cool air
temperature
trigger
30
00
Standard
○
Adjust the cool air trigger temperature. To
lower the trigger temperature, use setting
01. To raise the trigger temperature, use
setting 02.
01 Adjust (1)
02 Adjust (2)
Heat air
temperature
trigger
31
00
Standard
○
Adjust the heat air trigger temperature.
To lower the trigger temperature by 6
degrees C, use setting 01. To lower the
trigger temperature by 4 degrees C, use
setting 02. To raise the trigger tempera-
ture, use setting 03.
01 Adjust (1)
02 Adjust (2)
03 Adjust (3)
Auto restart 40
00 Enable
Enable or disable automatic system
restart after a power outage.
01 Disable
○
Cool Air
Prevention
43
00 Super low
○
Restrain the cold airfl ow with making
the airfl ow lower when starting
heating operation. To correspond to
the ventilation, set to 01.
01
Follow the
setting on
the remote
controller
External
control
46
00 Start/Stop
○
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed from
an external controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor unit stops by
the input to the external input terminals,
and Start/Stop by a remote controller is
restricted.
01
Emergency
stop
02 Forced stop
Error report
target
47
00 All
○
Change the target for reporting errors. Er-
rors can either be reported in all locations,
or only on the central remote controller.
01
Display only on
central remote
controller
Fan set-
ting when
cooling
thermostat
OFF
49
00
Follow the
setting on
the remote
controller
○
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired re-
mote controller (2-wire type or 3-wire
type) and switching its thermistor are
necessary.
01
Stop
Switching
functions
for external
inputs and
external
outputs
terminals
60
00 Mode 0
○
• Set this function when connecting
the VRF system to a ventilator, econ-
omizer, humidifi er, or other external
device.
• The connection terminal functions
can be changed depending on the
type of external device. For details
of the connection terminal functions,
see the Design & Technical Manual.
01 Mode 1
02 Mode 2
03 Mode 3
04 Mode 4
05 Mode 5
06 Mode 6
07 Mode 7
08 Mode 8
Control
switching
of external
heaters
61
00
Auxiliary
heater con-
trol 1
○
Sets the control method for the exter-
nal heater being used. For details of
the control method, see the Design &
Technical Manual.
01
Auxiliary
heater con-
trol 2
02
Heat pump
prohibition
control
03
Heater selec-
tion control
using outdoor
temperature 1
04
Heater selec-
tion control
using outdoor
temperature 2
Operating
tem-
perature
switching
of external
heaters
62
00 Setting 0
○
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions, see
"Temperature conditions when the
external heater is ON". For a more
detailed explanation, see the Design
& Technical Manual.
01 Setting 1
02 Setting 2
03 Setting 3
04 Setting 4
05 Setting 5
Temperature conditions when the external heater is ON
Temperature (t) when the external heater is ON= Room temperature - set temperature
Set value of function: 61
00 01 02 03 04
Set value of
function: 62
00 t < -5.4°F (-3°C) t ≤ -0.9°F (-0.5°C)
01 t < -3.6°F (-2°C) t ≤ -1.8°F (-1°C)
02 t < -3.6°F (-2°C) t ≤ -3.6°F (-2°C)
03 t < -5.4°F (-3°C) t ≤ -5.4°F (-3°C)
04 t < -7.2°F (-4°C) t ≤ -7.2°F (-4°C)
05 t < -9.0°F (-5°C) t ≤ -9.0°F (-5°C)
8.
TEST RUN
8.1. Test run using Outdoor unit (PCB)
• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
8.2. Test run using remote controller
• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER fl ash slowly at
the same time.
For details, please refer to the Manual of “IR Receiver Unit” or “Wired Remote Controller”.
9.
CHECK LIST
Pay special attention to the check items below when installing the indoor unit(s). After in-
stallation is complete, be sure to check the following check items again.
Check items If not performed correctly
Check
box
Has the indoor unit been installed cor-
rectly?
Vibration, noise, indoor unit may drop
Has there been a check for gas leaks
(refrigerant pipes)?
No cooling, No heating
Has heat insulation work been com-
pleted?
Water leakage
Does water drain easily from the indoor
units?
Water leakage
Is the voltage of the power source the
same as that indicated on the label on
the indoor unit?
No operation, heat or burn damage
Are the wires and pipes all connected
completely?
No operation, heat or burn damage
Is the indoor unit earthed (grounded)? Short circuit
Is the connection cable the specifi ed
thickness?
No operation, heat or burn damage
Are the inlets and outlets free of any
obstacles?
No cooling, No heating
Does start and stop air conditioner op-
eration by remote controller or external
device?
No operation
After installation is completed, has the
proper operation and handling been
explained to the user?