EasyManuals Logo

Fujitsu AMUG24LMAS Design & Technical Manual

Fujitsu AMUG24LMAS
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
¢
Indoor unit fan operation status
Function
setting /
Rotary SW of External
input and output PCB
External output Output signal Command
60-10 / C Output of indoor unit CN47
Low → High Fan run
High → Low Fan stop
60-00 / 2
60-01 / 3
60-05 / 7
60-06 / 8
60-09 / B
60-11 / D
External input and output
PCB
Output 2
Off → On Fan run
On → Off Fan stop
60-00 / 1 Output 3
Off → On Fan run
On → Off Fan stop
Output signal Condition
On
The indoor unit fan is operating.
Low → High
Off The fan is stopped or during cold air prevention.
High → Low During thermostat off when in dry mode operation.
Fan run
Fan stop
High
Low
CN47
On
Off
Output 2, 3
Indoor unit
- 32 -
6-4. Details of function 6. External input and output
DUCT TYPE
AMUG24-48LMAS
DUCT TYPE
AMUG24-48LMAS