Outdoor unit installation in multi-row
Unit: in (mm)
Single parallel unit arrangement Multiple parallel unit arrangement
6 (150) or more
24 (600) or more
40 (1000) or more
79 (2000)
or more
20 (500) or more
24 (600) or more
60 (1500) or more
119 (3000) or more
NOTES:
If the space is larger than stated above, the condition will be the same as when there is no ob-
stacle.
Height above the floor level should be 2 in (50 mm) or more.
When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
- 76 -
3-2. Models: AOUG36LMAS1 and AOUG48LMAS1 3. Installation space
OUTDOOR UNIT
AOU24-30RGLX,
AOUG36-48LMAS1
OUTDOOR UNIT
AOU24-30RGLX,
AOUG36-48LMAS1