01-05
Note: Specifications are based on the following conditions.
Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 100 Pa.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
dimensions( )* are indicated the including flange,control box,safety drain pan.
ART45LUAK ART54LUAK
AOT45LJAYL AOT54LJAYL
kW 12.5 / 14.0 14.5 / 15.3
BTU/h 42700 / 47800 49500 / 52200
kW 14.0 / 18.0 16.0 / 20.0
BTU/h 47800 / 61500 54600 / 68300
COOLING RATED / MAX 4.30 / 5.35 5.57 / 6.15
HEATING RATED / MAX 3.80 / 5.35 4.70 / 6.15
COOLING RATED / MAX 18.1 / 22.5 23.5 / 25.9
HEATING RATED / MAX 16.0 / 22.5 19.8 / 25.9
A 15 15
EER COOLING 2.91 2.61
COP HEATING 3.68 3.40
l/h (pints/h) 3.0 (1.4) 4.0 (1.9)
High
Med
Low
QUIET
High
Low
High
Med
Low
QUIET
High
Low
Pa 100 to 250 100 to 250
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
52 / 53 52 / 53
W 2500 2500
Corrosion resistant coating
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
UPPER FAN : 850 LOWER FAN : 750
RECOMMENDED STATIC PRESSURE
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
LIQUID
GAS
m
m
CHARGE g 3400 3400
COOLING
HEATING
WIRED WIRED
mm
REMOTE CONTROLLER
DRAIN PIPE
MATERIAL Steel
SIZE Outer diameter 25.4 / Inner diameter 21.5
REFRIGERANT OIL TYPE Synthetic (POE oil)
OPERATION(OUTDOOR)
-10 to 43
-15 to 24
REFRIGERANT
TYPE R410A
PIPE
CONNECTION METHOD FLARE
SIZE mm
9.52 (3/8 inc.)
15.88 (5/8 inc.)
MAX LENGTH 70 (chargeless:20m)
MAX HEIGHT 30
WEIGHT
NET /
GROSS
kg(lbs)
50 (110) / 55 (121)
105 (231) / 112 (247)
DIMENSIONS
H ×W ×D
NET
mm
400 × 1050(1150)* × 500(585)*
1290 x 900 x 330
GROSS
460 × 1230 × 640
1430 x 1050 x 445
CASING COLOR
Hot-dipped galvanized steel sheet
Beige(10YR7.5/1.0NN)
SAFETY DEVICES
Fan motor thermal protector,Fuse
Fan motor thermal protector,Fuse