08-11
DIP SWITCH SETTING
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
( Factory setting)
Decide the heating temperature correct coefficient vale of heating.
TEMPERATURE CORRECTION
In case of installing in high(low) static, you can maximize(minimize) air flow and noise.
Model:AR*24
This setting can be used when the auxiliary heater is mounted.
When the fan operation is stopped when the indoor unit is operating with an auxiliary heater,
the fan operation continues one minutes.
SW 1-1 SW state
OFF Invalidity
ON Validity
-2 deg
0 deg
0 deg
-2 deg
-2 deg
0 deg
0 deg
-2 deg
SW 1-2 SW 1-3
heating dry cooling
SW state
ON
ON ON
OFF
ON
0 deg
+4 deg
OFF
OFF
+2 deg
-2 deg
OFF
SW 4-1 OFF
ON Low static pressure
SW 4-2
OFF Normal
SW state
SW 4-3 SW state
ValidityON
OFF Invalidity
1-1.Auto restart setting
1-2.Room temperature correct coefficient of heating.
4-1.Dip SW 4-1setting forbidden
4-2.High(Low) static pressure function setting
4-3.Fan delay setting
( Factory setting)
( Factory setting)
( Factory setting)
( Factory setting)